1. Right of Way Clearance (As per GETCO Standard) 2. Minimum clearances between Electrical Lines crossing each other 3. Permissible Min ground Clearance of Electrical Line 4. Clearance for Telephone line Crossings Power Line 5. Vertical Clearance between Electrical Line and railway tracks 6. Clearance from Buildings to low, medium & high voltage lines 7. Clearance above ground at the lowest conductor 8. Vertical Clearance at Middle of Span 9. Safety Clearance from Live Part in Outdoor Substation 10. Lying of Telecommunication Cables with Power Cables (>33 kV) 11. Safe approach limits for people Code: Indian Electricity Rules / Central Electricity Authority Right of Way Clearance (As per GETCO Standard) KV Min ROW 66 KV 18 Meter 132 KV 27 Meter 220 KV 35 Meter 400KV 52 Meter (Single Circuit) 400 KV 48 Meter (Double Circuit) Go to Content Minimum clearances between Electrical Lines crossing each other Voltage 66 KV 132 KV 220 KV 400 KV 66 KV 2.4 Meter 3 Meter 4.5 Meter 5.4 Meter 132 KV 3 Meter 3 Meter 4.5 Meter 5.4 Meter 220 KV 4.5 Meter 4.5 Meter 4.5 Meter 5.4 Meter