Unformatted text preview: Problem discussed: A 9 MGD aerobic activated sludge has three aerobic digesters. They had been receiving around 90000 gallons of thickened WAS for 15 months and now cause lot of offensive odor. This has created nuisance in the place. Summary of the thread: The thread suggests that the problem is basically due to overloading of the activated sludge. The postings on the thread say that the insufficient amount of oxygen for the higher percentage of total solids (3.5% to 4%) in the plant can cause such a problem. Source of the odor can be organic acids (acetic acids, lactic acids, propionic acids etc...). If the tank is septic, then the major source of the odor can be organic sulfur compounds. Dewatering, lime stabilizing and dumping of the sludge to avoid the overloading of the activated sludge can be helpful in arresting the problem. Suggestions: Reduce Concentration of Waste Activated Sludge (WAS) As suggested in this thread, the foul odors could be due to the aerobic digesters going septic as a...