Unformatted text preview: Question 1 4 / 4 points It is not permitted to use round boxes to make conduit connections that depend on locknuts and bushings when connections are made _____. to sides of box Question 2 4 / 4 points A 4 - 11/16 inch square by 2 1/8 inch deep outlet box will have a cubic inch capacity of ________. 42 cu. in. Question 3 4 / 4 points The maximum number of #10 conductors permitted in a 4 inch square by 2 1/8 inch deep outlet box would be _______. 12 Question 4 4 / 4 points Where (6) #14 conductors enters a box in one conduit and (2) of those conductors pass through without splicing or terminating into another conduit that has (4) other #14 conductors, the minimum cubic inch capacity for this box would be ___. 20 Question 5 4 / 4 points Where #12 conductors are connected to a receptacle the minimum cubic inch device fill for an outlet box would be ______. 4.5 cu. in. Question 6 4 / 4 points Where an outlet box is equipped with two internal clamps and #12 and #10 conductors are used in that...