lecture10- Generation with Limited Energy Supply

Lecture10- - EEL 6266 Power System Operation and Control Chapter 6 Generation with Limited Energy Supply © 2002 2004 Florida State University EEL

Info iconThis preview shows pages 1–7. Sign up to view the full content.

View Full Document Right Arrow Icon

Info iconThis preview has intentionally blurred sections. Sign up to view the full version.

View Full DocumentRight Arrow Icon

Info iconThis preview has intentionally blurred sections. Sign up to view the full version.

View Full DocumentRight Arrow Icon

Info iconThis preview has intentionally blurred sections. Sign up to view the full version.

View Full DocumentRight Arrow Icon
This is the end of the preview. Sign up to access the rest of the document.

Unformatted text preview: EEL 6266 Power System Operation and Control Chapter 6 Generation with Limited Energy Supply © 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 2 Generation with Limited Energy Supply c Hard limits and slack variables r take account of the limits on the take-or-pay generating unit r this may be added to the Lagrangian by using two new functions and two new variables, called slack variables c where S 1 j and S 2 j are the slack variables c they may take on any real value including zero r the new Lagrangian max min T T T P P P ≤ ≤ ( 29 ( 29 ( 29 ∑ ∑ ∑ ∑ ∑ ∑ ∑ = = = = = = = +- + +- + - + -- + = max max max max max 1 2 2 min 2 1 2 1 max 1 1 1 1 , 1 1 j j j j T T j j j j T j T j total j j j T j j j N i j T j i j load j N i j i j j j S P P S P P q q n P P P F n L α α γ λ 2 2 min 2 2 1 max 1 and j j T T j j T j T j S P P S P P +- = +- = ψ ψ © 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 3 Generation with Limited Energy Supply c Hard limits and slack variables r α 1 j and α 2 j are Lagrange multipliers r the first partial derivatives for the k th interval are c when the constrained variable P Tk is within bounds, α 1 j = α 2 j = 0 and S 1 j and S 2 j are nonzero; when P Tk is limited, either S 1 j or S 2 j is zero and the associated Lagrange multiplier is nonzero k k k k k k k k k k T k T k k T k k i k i k k i S L S L P q n P L P F n P L 2 2 2 1 1 1 2 1 2 2 d d d d α α α α α α λ γ λ = = ∂ ∂ = = ∂ ∂- +- = = ∂ ∂- = = ∂ ∂ © 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 4 Generation with Limited Energy Supply c Hard limits and slack variables r consider some interval k where P Tk = P max c S 1 k = 0 and α 1 k ≠ 0, then c if the value of α 1 k takes on the value just sufficient to make the equality true d d 1 = + +- k T k T k k k P q n γ α λ k T k T k k P q n d d γ λ © 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 5 Generation with Limited Energy Supply c Example r reconsider the 6-interval 24-hour fuel scheduling c maximum generation on P T is reduced to 300 MW s in the original optimal schedule, P T = 353.3 in the third time- period s when the limit is reduced to 300 MW, the gas-fired unit burns more fuel in other time periods to meet the 40 M ft 3 gas consumption constraint © 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 6 Generation with Limited Energy Supply c Example r resulting optimal schedule with Ptmax = 300 MW c shadow price, γ : 0.8603 c total cost: $ 122,985 1 183.4 216.6 5.54 5.54 0....
View Full Document

This note was uploaded on 07/15/2011 for the course EEL 6266 taught by Professor Thomasbaldwin during the Fall '04 term at FSU.

Page1 / 27

Lecture10- - EEL 6266 Power System Operation and Control Chapter 6 Generation with Limited Energy Supply © 2002 2004 Florida State University EEL

This preview shows document pages 1 - 7. Sign up to view the full document.

View Full Document Right Arrow Icon
Ask a homework question - tutors are online