Lecture 19 Balance Fault Analysis, Symmetrical Components Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS
Background image of page 1

Info iconThis preview has intentionally blurred sections. Sign up to view the full version.

View Full DocumentRight Arrow Icon
2 Announcements Be reading Chapter 8 HW 8 is 7.6, 7.13, 7.19, 7.28; due Nov 3 in class. Start working on Design Project. Tentatively due Nov 17 in class.
Background image of page 2
3 In the News Earlier this week the Illinois House and Senate overrode the Governor’s veto of the Smart Grid Bill; it is now law On Tuesday Quinn called it a “smart greed” plan Law authorizes a ten year, $3 billion project to “modernization” the electric grid in Illinois All ComEd customers and most of Ameren will get “smart” meters Effort will be paid for through rate increases over the period; ComEd estimated the average increase of $36 per year would be offset by electricity savings
Background image of page 3

Info iconThis preview has intentionally blurred sections. Sign up to view the full version.

View Full DocumentRight Arrow Icon
4 Network Fault Analysis Simplifications To simplify analysis of fault currents in networks we'll make several simplifications: 1. Transmission lines are represented by their series reactance 2. Transformers are represented by their leakage reactances 3. Synchronous machines are modeled as a constant voltage behind direct-axis subtransient reactance 4. Induction motors are ignored or treated as synchronous machines 5. Other (nonspinning) loads are ignored
Background image of page 4
5 Network Fault Example For the following network assume a fault on the terminal of the generator; all data is per unit except for the transmission line reactance 2 19.5 Convert to per unit: 0.1 per unit 138 100 line X = = generator has 1.05 supplies 100 MVA with 0.95 lag pf
Background image of page 5

Info iconThis preview has intentionally blurred sections. Sign up to view the full version.

View Full DocumentRight Arrow Icon
6 Network Fault Example, cont'd Faulted network per unit diagram * ' a To determine the fault current we need to first estimate the internal voltages for the generator and motor For the generator 1.05, 1.0 18.2 1.0 18.2 0.952 18.2 E 1.103 7.1 1.05 T G Gen V S I = = ° = = ∠ - ° = ° ÷
Background image of page 6
7 Network Fault Example, cont'd f The motor's terminal voltage is then 1.05 0 - (0.9044 - 0.2973) 0.3 1.00 15.8 The motor's internal voltage is 1.00 15.8 (0.9044 - 0.2973) 0.2 1.008 26.6 We can then solve as a linear circuit: 1 I j j j j × = ∠ - ° ∠ - ° - × = ∠ - ° = .103 7.1 1.008 26.6 0.15 0.5 7.353 82.9 2.016 116.6 9.09 j j j ° ∠ - ° + = ∠ - ° + ∠ - ° =
Background image of page 7

Info iconThis preview has intentionally blurred sections. Sign up to view the full version.

View Full DocumentRight Arrow Icon
8 Fault Analysis Solution Techniques Circuit models used during the fault allow the network to be represented as a linear circuit There are two main methods for solving for fault currents: 1. Direct method: Use prefault conditions to solve for the internal machine voltages; then apply fault and solve
Background image of page 8
Image of page 9
This is the end of the preview. Sign up to access the rest of the document.

This note was uploaded on 11/17/2011 for the course ECE 476 taught by Professor Overbye,t during the Fall '08 term at University of Illinois, Urbana Champaign.

Page1 / 29

ECE4762011_Lect19 - ECE 476 POWER SYSTEM ANALYSIS Lecture...

This preview shows document pages 1 - 9. Sign up to view the full document.

View Full Document Right Arrow Icon
Ask a homework question - tutors are online