Project Number 1 Section 16410 Project Name Project Date Enclosed Switches And Circuit Breakers SECTION 16410 ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install disconnects as described in Contract Documents, except those provided integral with equipment. B. Related Sections 1. Section 16051 - General Electrical Requirements PART 2 PRODUCTS 2.1 EQUIPMENT A. Disconnects 1. Heavy duty quick-make, quick-break type, non-fused unless indicated otherwise. 2. Provide interlock to prevent opening of door when switch is in ON position. 3. Provide means to lock switch in OFF position with padlock. 4. Disconnects for motor circuits shall be horsepower rated Delete or edit paragraph ‘5' if no furnaces on Project. Include paragraph ‘5’ if furnaces ARE NOT provided with internal overload devices. Delete paragraph ‘5' If furnaces ARE provided with internal overload protection devices.