Project Number 1 Section 16441 Project Name Project Date Switchboards SECTION 16441 SWITCHBOARDS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install switchboards as described in Contract Documents. B. Related Sections 1. Section 16051 - General Electrical Requirements PART 2 PRODUCTS 2.1 EQUIPMENT Use of circuit breaker equipment is preferred over fuses wherever possible. Obtain available fault current at Project from power company and adjust specified short circuit ratings as necessary. Inform power company of expected low peak demand for Project so main service transformer is not oversized. A. Main Switchboard 1. Minimum integrated equipment short circuit rating of 100,000 amperes. 2. Enclosures - OPTION ONE - Include this optional requirement if switchboard is on the EXTERIOR of building. NEMA Type 3R with locking door OPTION TWO - Include this optional requirement if switchboard is on the INTERIOR of building. NEMA Type 1