Mathcad - 07-03

Mathcad - 07-03 - S 212.7KVA = S 3 I l V l = I l S 3 V l =...

Info iconThis preview shows page 1. Sign up to view the full content.

View Full Document Right Arrow Icon
rev 1 poles 1 KVA kW Problem 7-3 Solution: From the NEC Table 430-7, for code letter H, the KVA/HP at starting (locked rotor) has a maximum value of 7.09. V l 230 volt = Hp 30 hp = K 7.09 KVA hp = S K Hp = S 7.09 KVA hp 30 hp =
Background image of page 1
This is the end of the preview. Sign up to access the rest of the document.

Unformatted text preview: S 212.7KVA = S 3 I l V l = I l S 3 V l = I l 212.7 KVA 3 230 volt = I l 533.923amp = NOTE: rated current for this machine would be about 80 amps according to the NEC...