All Lectures

Office spaces shall have maximum lighting power

Info iconThis preview shows page 1. Sign up to view the full content.

View Full Document Right Arrow Icon
This is the end of the preview. Sign up to access the rest of the document.

Unformatted text preview: ents using a “componentbased” approach. For example: • Exterior walls shall have a minimum thermal resistance of R-15. • Office spaces shall have maximum lighting power density of 10 W/m2. • Washroom faucets in public building shall have automatic shut-off (e.g. to conserve hot water). Note: The above are only examples of the types of requirements. (The actual requirements for each component are listed within the code/standard.) Aside: Code requirements are typically based on cost-effective good-practice for “typical” building conditions. However, for some specialized building types, application of the code requirements may not be suitable/practical. (End of Aside.) Both codes used two basic types of requirements: “Mandatory Requirements” • A minimum level of performance that must be met by all designs. “Prescriptive Requirements” • Define a “reference level” of performance. • Comply either by meeting each individual prescriptive requirement, or by demonstrating the design will not use more energy than a design that did meet each individual prescriptive requirement. • Provides some flexibility in design (“trade-offs”). STRUCTURE OF MNECB 1997 Mandatory Provisions Building Envelope Lighting Service Water Htg HVAC Prescriptive Path Electrical & Power Performance Path Building Envelope Trade-Offs Trade-Offs Prescriptive (simple) (computer) Building Energy Performance (Simulation) Lighting HVAC NO Service Water Heating REDESIGN Compliance? YES Example of Application of Mandatory and Prescriptive Code Provisions: Imagine an extremely simple building where applicable code provisions are only as follows: Mandatory Provisions 1. Maximum allowable flow-rate of shower-heads is 9.0 L/min. Prescriptive Provisions 1. Maximum thermal transmittance (U-value) of exterior walls = 0.38 W/m2-°C. 2. Minimum efficiency of furnace = 85%. outdoors flue Furnace Heated Space fuel heat loss through exterior wall with thermal transmittance = heat input from heating device with efficiency = Mandatory Provisions… Shower-head flowrate must be 9.0 L/min or less. (Cannot “trade-off” versus other provisions.) Any design with showerhead flowrate higher than 9.0 L/min would not comply—no matter how “efficient” the other components of the building were made. Prescriptive Provisions… Characteristic Design A Design B Design C Design D Wall U-value (W/m2-°C) 0.38 0.30 0.30 0.50 Furnace Efficiency 85% 85% 80% 95% Complies? Yes. Yes. ? ? Prescriptive Performance Path (simulation) Performance Path (simulation) Compliance Method? Prescriptive “Reference Design” Compare to performance of “Reference Design” (i.e. design that exactly meets prescriptive provisions) Sample Requirements from MNECB 1997: BUILDING ENVELOPE Mandatory Requirement: Vestibules are required at exterior doors. (Some doors are exempted from this requirement—as described in the Code). Prescriptive Requirement: Maximum Overall Thermal Transmittance (U-value), W/m2-°C “Ontario Region A” (Southern Ontario) Component Above Ground Walls Heating Source Electricity Natural Gas 0.330 0.550 Sample Requirements from MNECB 1997: LIGHTING Mandatory Requirement: Exterior lights shall be controlled by a lighting schedule controller (timer) or by a photocell (daylight sensor). Prescriptive Requirement: Maximum Allowable Lighting Power Density (W/m2) by Space-Type Space Type LPD (W/m2) Laboratory 24.8 Classrooms 21.5 Gymnasium 10.8 Jail Cell 8.6 Sample Requirements from MNECB 1997: HVAC Mandatory Requirement: Systems shall have controls capable of reducing energy use through temperature set-back or equipment shut-down during periods of non-use (with some exceptions). Prescriptive Requirement: HVAC systems shall utilize outside-air economizers (with some exceptions). Sample Requirements from MNECB 1997: SERVICE WATER HEATING Mandatory Requirement: Faucets in public access washroom shall have a device capable of automatically shutting off the flow of water when the faucet is not in use (e.g. motion sensor or spring-return valve). ELECTRICAL POWER Mandatory Requirement: Electrical transformers shall conform to CAN/CSA-C802 “Maximum Losses for Distribution, Power, and Dry-Type Transfomers” where the installed transformer falls within the scope of the standard. (CAN/CSA-C802 includes minimum requirements for transformer efficiency.) Typical Procedures for “Performance Compliance Analysis” • Usually hour-by-hour simulations are performed to compare performance of “proposed design” vs the code “reference design” (i.e. prescriptive design) • In general, any characteristics not covered by Prescriptive Requirements are treated identically – – – – Size and use of building Operating schedules (occupants, lighting, plug loads, etc) Minimum fresh air rates (ventilation) Area and orientation of exterior envelope components (with some exceptions) For Example: “EE4” Software • Hour-by-hour simulation tool intended comparing “Proposed Design” to MNECB for • Simulator describes characteristics of the “Proposed Design” – Software performs simulation of the “Proposed Design” – Software automatically creates a second simulation file – the “Reference Design” simulation, which is identical to the proposed design, except that it uses the relevant pre...
View Full Document

This note was uploaded on 10/04/2012 for the course ME 760 taught by Professor Davidmather during the Spring '12 term at Waterloo.

Ask a homework question - tutors are online