Building Code of the Philippines(1)

Shall be such that in the event of failure of the

Info iconThis preview shows page 1. Sign up to view the full content.

View Full Document Right Arrow Icon
This is the end of the preview. Sign up to access the rest of the document.

Unformatted text preview: the prime mover on failure of the normal service shall be provided. For hospitals, the transition-time from instant of failure of the normal power source to the emergency generator source shall not exceed ten seconds. (See Section 12.4). 12.9 There shall be two services, each in accordance with Section 200 of the PEC, widely separated electrically and physically to minimize the possibility of simultaneous interruption of power supply arising from an occurrence within the building or group of buildings served. 12.10 Connections on the line side of the main service shall be sufficiently separated from said main service to prevent simultaneous interruption of supply through an occurrence within the building or group of buildings served. 12.11 The requirements of Section 12.5 and Section 12.6 also apply to installations where the entire electrical load on a service or sub-service is arranged to be supplied from a second source. Current supply from a standby power plant shall satisfy the requirements of availability in Section 12.6. 12.12 Audible and visual sign devices shall be provided, where practicable, for the following purposes: a) To give warning of dearrangement of the emergency or auxiliary source. b) To indicate that the battery or generator set is carrying a load. c) To indicate when a battery charges is properly functioning. 12.13 Only appliances and lamps specified as required for emergency use shall be supplied by emergency lighting circuits. 12.14 Emergency illumination shall be provided for all required exit lights and all other lights specified as necessary for sufficient illumination. Emergency lighting systems should be so designed and installed that the failure of any individual lighting element, such as the burning out of a light bulb, shall not leave any area in total darkness. 12.15 Branch circuits intended to supply emergency lighting shall be so installed as to provide service immediately when the normal supply for lighting is interrupted. Such installations shall provide either one of the following: a) An emergency lighting supply, independent of the general lighting system with provisions for automatically transferring to the emergency lights by means of devices approved for the purpose upon the event of failure of the general lighting system supply. b) Two or more separate and complete systems with independent power supply, each system providing sufficient current for emergency lighting purposes. Unless both systems are used for regular lighting purposes and are both lighted, means shall be provided for automatically energizing either system upon failure of the other. Either or both systems may be part of the general lighting system of the protected occupancy if circuits supplying lights for emergency illumination are installed in accordance with other Sections of this Rule. 12.16 For branch circuits which supply equipment classed as emergency, there shall be an emergency supply source to which the load will be transferred automa...
View Full Document

This note was uploaded on 09/22/2013 for the course ARIDBE AR taught by Professor Any during the Fall '12 term at Mapúa Institute of Technology.

Ask a homework question - tutors are online