© PMA of Georgia 2010Venting 901.2 Trap seal protection. The plumbing system shall be provided with a system of vent piping that will permit the admission or emission of air so that the seal of any fixture trap shall not be subjected to a pneumatic pressure differential of more than 1 inch of water column (249 Pa).In this code section we are told that “The plumbing system shall be provided with a system of vent piping that will permit the admission or emission of air”.The plumbing system needs to breath. The second half of this section tells us why the plumbing systemneeds to breath. “so that the seal of any fixture trap shall not be subjected to a pneumatic pressure differential of more than 1 inch of water column (249 Pa).”Here we are told that the protection of the seal is the reason for the vent, (the reason the system needs to breath).
Background image
© PMA of Georgia 2010Venting The seal of any fixture trap shall not be subjected to a pneumatic pressure differential of more than 1 inch of water column (249 Pa).12 inches of water column equals0.433 psig. 1 inch of water columnequals 0.036 psig.This also refers to half of the trap sealwhich shall be at least two inches.Trap sealWith an atmospheric pressure of approximately 14.7 psi at sea level, there can be no more than plus or minus 0.036 psig difference present between both sides of the trap seal
Background image
© PMA of Georgia 2010Venting 901.2.1 Venting required. Every trap and trapped fixture shall be vented in accordance with one of the venting methods specified in this chapter.In this presentation we will look at the venting methods which are specified in chapter 9 of the International Plumbing Code 2006 edition. Also the 2007 Georgia State Amendments.
Background image
© PMA of Georgia 2010903.1 Required vent extension. The vent system serving each building drain shall have at least one vent pipe that extends tothe outdoors.903.1.1 Installation. The required vent shall be a dry vent that connects to the building drain or an extension of a drain that connects to the building drain. Such vent shall not be an islandfixture vent as allowed by Section 913.903.1.2 Size. The required vent shall be sized in accordance with Section 916.2 based on the required size of the building drain.SECTION 903OUTDOOR VENT EXTENSION
Background image
© PMA of Georgia 2010904.1 Roof extension. All open vent pipes that extend through a roof shall be terminated at least [NUMBER] inches (mm) above the roof, except that where a roof is to be used for any purpose other than weather protection, the vent extensions shall be run at least 7 feet (2134 mm) above the roof.SECTION 904VENT TERMINALSRoof used as sundeck7’The 2007 amendments tell us to insert the number 6 for [NUMBER] in this section.6”
Background image
© PMA of Georgia 2010904.5 Location of vent terminal. An open vent terminal from a drainage system shall not be located directly beneath any door, openable window, or other air intake opening of the building or of an adjacent building, and any such vent terminal shall not be within 10 feet (3048 mm) horizontally of such an opening unless it is at least 2 feet (610 mm) above the top of such opening.
Background image