Figure ## Phillips RC486B W62L62 VPC
1xLED78S/TWH-6700 AC-MLO
Luminaire
RC132V W30L60
PSU 1 xLED18S/840
NOC
Light Output Ratio
99.90%
Lamp Luminous Flux
4300 lm
Luminaire Luminous
Flux
4296 lm
Power
45.0 W
Luminous Efficacy
95.5 lm/W
Colorimetric Data
*copy sa nighttime
floor report*
Table ## Phillips RC486B W62L62 VPC
1xLED78S/TWH-6700 AC-MLO – Datasheet
Figure ## Phillips RC486B W62L62 VPC
1xLED78S/TWH-6700 AC-MLO – Polar Intensity
Diagram
This luminaire was used due to it’s higher
luminous flux and wide distribution curve. This
resulted to a larger area being able to reach the
standards of the room.
Figure ## Phillips RS060B 1Xled5-36-/830
Luminaire
RC132V W30L60
PSU 1 xLED18S/840
NOC
Light Output Ratio
99.67%
Lamp Luminous Flux
480 lm
Luminaire Luminous
Flux
478 lm
Power
6.0 W
Luminous Efficacy
79.7 lm/W

UST: EE524L-T2AY1920-5EEB-G6
13
Colorimetric Data
*copy sa nighttime
floor report*
Table ## Phillips RS060B 1Xled5-36-/830 –
Datasheet
Figure ## Phillips RS060B 1Xled5-36-/830 –
Polar Intensity Diagram
This luminaire was used as an entry or exit light
for the door for the person inside or going inside
have visual of the area around the door. It was also
chosen for its small distribution curve in order to
lessen the overlapping of lighting at certain areas.
Figure ## Sacristy Luminaire – Light
Distribution Curve
Figure ## Sacristy – Luminaire Control
Utilizing a three-gang switch, three groups of luminaires
can be controlled depending on time and conditions.
Luminaire group one consists of luminaire numbers one, five,
six and three. They are primarily used during the night as the
areas they are located are reached by the sunlight during the
day. Luminaire group 2 controls luminaire 2 and 4 and can be
used during the day and night as the areas they are located far
from the windows. Luminaire group 3 controls luminaire 7
which is used at day and night as sunlight reaching the
couches are not enough.
c.
Daytime Data
Figure ## Sacristy – Daytime – 3D Render 1
Figure ## Sacristy – Daytime – 3D Render 2
Figure ## Sacristy – Daytime – Room – False
Color 1
Figure ## Sacristy – Daytime – Room – False
Color 2
i.
Working Plane
1
3
5
6
2
7
4

UST: EE524L-T2AY1920-5EEB-G6
14
Figure ## Sacristy – Daytime – Working Plane
– Combined Data 1
Figure ## Sacristy – Daytime – Working Plane
– Combined Data 2
The simulation was done under average sky
conditions at 12 noon with luminaire groups two and
three turned on. The room was able to obtain an
average illuminance value of 338 lux, meaning the
room was able to reach its standard of 300 lux.
Uniformity with the light distribution was also
observed in the important areas such as where the
chairs are located and the table where preparations
for the mass is made. Small pockets of lower
illuminance were present in the corners, but they can
be said as areas with little to no activities due to their
location and size. Lower values can also be seen in
the doors to the side, but it is meant to aid the eyes of
the person going in to gradually adjust to the amount
of light in the room.