d. All receptacles in patient service consoles, isolation nursing rooms, cystoscopy, IVP rooms, cardiac catheterization room, radiographic special procedure rooms, oral surgery room, and recovery rooms. Provide additional normal powered receptacles for backup of critical circuits. e. All receptacles in selected rooms in the surgery suite, the delivery suite, nursery, coronary care unit, intensive care units, hemodialysis, and emergency. f. All equipment for the refrigerated storage of blood, biological, pathology specimens and medicines. g. Two X-ray rooms (including one fluoroscopic room) and required automatic x- ray film processor station. h. Dental oral evacuation system and dental compressed air system. i. Laboratories, incubators, analysis, blood bank, bone and tissue banks, chemistry, hematology plus selected receptacles. j. One flash sterilizer in each surgical suite and delivery suit cluster core. © J. Paul Guyer 2010 22