PE Power Electrical Engineering Sample Exam1335.Figure 35 shows a synchronous generator connected to a synchronousmotor by a transmission line. Base values are 10 MVA, 12 kV.The motor voltage, VM, is 1 pu and the current, IM, is 1.1 pu at a leadingpower factor of 0.8. A symmetrical three-phase fault occurs at the terminalsof the motor. The contribution of the fault current from the generator in kAis nearly:a.1.92b.1.03c.0.78d.0.39
36.Consider this set of unbalanced, three-phase currents:/ = 125 Z50° amps/”=95 Z10° amps/ = 150 Z-110° ampsI, the positive-sequence component, is nearly:
Get answer to your question and much more
37.Positive-sequence and negative-sequence components of the line-to-linevoltage of a wye-connected load, V b are specified as 115Z-15° and30Z1050, respectively. The phase voltage |V| is nearly:
Get answer to your question and much more
38.The positive-, negative-, and zero-sequence reactances of a 40 MVA, 20kV synchronous generator are 0.45 pu, 0.25 pu, and 0.10 pu, respectively.The generator is solidly grounded and is not loaded when a line-to-ground fault occurs on phasea.(Neglect all the resistances.) The faultcurrent I in kA is nearly: