A 500 V/230 V single-phase transformer is rated at 30 kVA. The open circuit test results, with the instruments connected to the high voltage winding,...
This question has been answered
Question

A 500 V/230 V single-phase transformer is rated at 30 kVA.

The open circuit test results, with the instruments connected to the high voltage winding, are: 300 W, 3.5 A at 500 V, 50 Hz.


The short circuit test results, 230 V winding short circuited, and with the instruments still connected to the 500 V winding, are: 1500 W, full load current at 30V.

(a) Calculate the approximate equivalent circuit values.

(b) Draw the approximate equivalent circuit with the appropriate values referred to the high voltage winding.

(c) Draw the approximate equivalent circuit with the appropriate values when referred to the low voltage winding. 

Answered by Expert Tutors

ec facilisis. Pellente

dictum vitae odio. Donec aliquet. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Nam lacinia pulvinar tortor nec facilisis. Pellentesque dapibus efficitur laoreet. Nam risus ante, dapibus a molestie consequat, ultrices ac magna. Fusce dui lectus, congue vel laoreet ac, dictum vitae odio. Do
Step-by-step explanation

New Doc 2020-05-04 18.58.09_1_1588598974665.jpgNew Doc 2020-05-04 18.58.09_2_1588599097085.jpgNew Doc 2020-05-04 18.58.09_3.jpgac, dictum vitae odio. Donec aliquet. Lo

m ipsum dolor sit ame
3 Attachments
New Doc 2020-05-04 18.58.09_1_1588598974665.jpg
jpg
New Doc 2020-05-04 18.58.09_2_1588599097085.jpg
jpg
New Doc 2020-05-04 18.58.09_3.jpg
jpg
The student who asked this found it Helpful
Overall rating 100%

"Thanks alot :)"

Get unstuck

336,246 students got unstuck by Course
Hero in the last week

step by step solutions

Our Expert Tutors provide step by step solutions to help you excel in your courses